Sound insulation is an important but often overlooked aspect of building work. Part E of the Building Regulations sets minimum acoustic performance requirements for separating walls and floors between dwellings — and for certain walls and floors within single dwellings. Getting sound insulation right in an extension means choosing the correct construction and materials from the outset, not trying to retrofit acoustic improvements after the walls and floors are built. Crown Architecture & Structural Engineering designs extensions that meet Part E requirements across the UK. Call 07443804841 for acoustic advice on your project.
What Is Part E?
Approved Document E: Resistance to the Passage of Sound sets out the minimum sound insulation requirements for buildings in England. It covers:
- Separating walls and floors: The walls and floors between separate dwellings (terraced houses, semi-detached houses, flats) must achieve minimum airborne and impact sound insulation values
- Internal walls and floors in new dwellings: Walls between rooms and a bathroom/WC, and floors between rooms, must achieve minimum airborne sound insulation values in new dwellings
- Schools: Acoustic performance requirements for educational buildings (beyond the scope of this guide)
Part E requirements apply to material changes of use (e.g. converting a house to flats), new buildings, and material alterations (e.g. replacing an existing separating wall). For extensions to existing single houses (adding a rear extension to a family home), Part E’s separating wall and floor requirements are less commonly triggered — though good acoustic design principles should still be applied.
Airborne Sound vs Impact Sound
There are two types of sound transmission that acoustic insulation must address:
Airborne sound: Sound transmitted through the air — speech, music, TV, barking dogs. Measured by the DnT,w + Ctr value (weighted standardised level difference). Higher values mean better insulation (more sound stopped). Part E minimum for separating walls: DnT,w + Ctr ≥ 45 dB. For separating floors: DnT,w + Ctr ≥ 45 dB.
Impact sound: Sound transmitted through structure — footsteps, dropped objects. Measured by the L’nT,w value (weighted standardised impact sound pressure level). Lower values mean better insulation (less sound transmitted). Part E minimum for separating floors: L’nT,w ≤ 62 dB.
When Does Part E Apply to Extensions?
Extensions Creating Additional Dwellings
If your extension creates a new separate dwelling — for example, a granny annexe with its own entrance and facilities — the wall or floor separating the annexe from the main house becomes a “separating element” under Part E and must achieve the minimum acoustic performance values. This is a significant design consideration that must be addressed from the outset.
House-to-Flat Conversions
As described in our conversion guide, converting a house into flats requires full Part E compliance for the separating floors and walls between the flats. This typically requires significant upgrading of existing timber floors and walls, plus pre-completion acoustic testing to verify compliance.
Extensions to Semi-Detached and Terraced Houses
For extensions to semi-detached or terraced houses, the existing party wall (separating wall shared with the neighbour) already has Part E status. Carrying out works that would reduce the existing acoustic performance — for example, removing part of the existing wall without rebuilding it to equivalent acoustic standard — would trigger the requirement to reinstate the acoustic performance. In practice, most rear extensions do not affect the party wall and so do not directly trigger new Part E obligations.
Internal Acoustic Standards
For new dwellings (including new granny annexes treated as new dwellings), Part E requires internal walls between a habitable room and a bathroom or WC to achieve an airborne sound insulation of Rw ≥ 40 dB. This requires more than a simple timber stud partition — a lined, insulated stud wall with acoustic board is the typical solution.
Achieving Part E Compliance: Separating Walls
For a new separating wall between a converted annexe and the main house, typical compliant constructions include:
- Masonry (cavity wall, min 100mm dense block leaves): Two leaves of 100mm dense aggregate block (1800 kg/m³+) with a 50mm cavity — suitable for the separating wall between an annexe and the main house. The mass of the masonry provides the airborne sound insulation. Typical DnT,w + Ctr of 52–55 dB when correctly built.
- Masonry with additional lining: A 100mm dense block wall with an independent plasterboard and mineral wool lining on one or both faces. The combination of mass and the absorption of the cavity/lining improves performance further.
- Timber frame with acoustic lining: Not typically suitable for separating walls between dwellings without extensive acoustic treatment — the lack of mass in a timber frame requires multiple layers of dense plasterboard and acoustic insulation to approach the required performance.
Achieving Part E Compliance: Separating Floors
For floors between a converted annexe above and a room below (or between flats), typical compliant constructions include:
For new concrete separating floors: A 150mm solid reinforced concrete slab with a resilient floor finish (e.g. 18mm T&G board on resilient battens or a proprietary resilient layer) and a 100–150mm ceiling treatment (plasterboard on independent ceiling hangers) typically achieves the required airborne and impact values.
For existing timber separating floors (in a conversion): The existing floor structure typically requires upgrading:
- Adding mass to the floor (a dry screed system or heavy boards over the existing boards)
- Adding a resilient layer (floating floor system) to reduce impact transmission
- Adding acoustic quilt between joists
- Independent ceiling (resilient bars or acoustic ceiling hangers, isolated from the floor structure above)
All four elements together provide the best compliance — omitting any element reduces performance and risks failing the pre-completion test.
Pre-Completion Acoustic Testing
Part E requires pre-completion sound insulation testing for new separating walls and floors in England (with some exceptions for low-risk situations where robust details are used). Testing must be carried out by a competent person, following ADE Annex B test method, before the building is occupied. Results must be submitted to Building Control as part of the completion process.
If tests fail, Building Control will not issue a Completion Certificate until remediation is carried out and the tests pass. Remedial work to improve sound insulation after walls and floors are built is expensive and disruptive — this is why getting the construction right from the outset is so important.
Robust Details
Approved Document E includes a set of “robust details” — standard construction specifications that, if followed precisely, are deemed to comply with Part E without requiring pre-completion testing. Using a robust detail specification exempts the construction from the testing requirement. However, robust details are only available for specific construction types and must be followed exactly — deviations invalidate the exemption.
The Robust Details Ltd (robustdetails.com) website provides the current list of approved details. Each robust detail requires the builder to register the use of the detail and carry out a specific quality monitoring process during construction.
Acoustic Insulation Beyond Part E Minimums
Part E minimum values are widely regarded as setting a low bar for acceptable acoustic privacy. Many homeowners — and many LPAs in their design policies — seek higher standards. The WHO (World Health Organisation) night noise guidelines for bedrooms, for example, suggest internal noise levels below 30 dB LAeq — significantly quieter than Part E alone will achieve in many urban environments.
For high-specification residential projects, acoustically sensitive locations (near roads, rail, or nightlife), or buildings with demanding acoustic requirements, Crown Architecture & Structural Engineering recommends engaging an acoustic consultant to carry out a detailed noise assessment and design bespoke acoustic solutions above the Part E minimum.
Frequently Asked Questions
Does my rear extension need to comply with Part E?
A standard rear extension to an existing single dwelling house (not creating a new separate dwelling) does not typically trigger Part E’s separating element requirements. Part E internal acoustic requirements apply to new dwellings or material changes of use — not to extensions that remain part of a single existing dwelling.
What is the difference between acoustic insulation and thermal insulation?
Thermal insulation reduces heat transfer through building elements (measured by U-value). Acoustic insulation reduces sound transmission through building elements (measured by DnT,w + Ctr for airborne sound). The materials used for each are different — dense mass (masonry, concrete) is effective for acoustic insulation but may have poor thermal properties; mineral wool insulation is good for both. Some products address both requirements; others are specialist acoustic materials.
Can acoustic insulation be added after the walls and floors are built?
Yes, but it is much more expensive and less effective than incorporating it in the original construction. Acoustic lining boards (dense plasterboard on resilient bars) can be added to walls; resilient floor systems can sometimes be installed over existing floors. However, flanking transmission (sound bypassing the treated element through the structural connections) often limits the improvement achievable in existing constructions.
Crown Architecture & Structural Engineering designs extensions and conversions with appropriate acoustic insulation for Part E compliance. Call 07443804841 for acoustic design advice on your project.